 EMC filters
4-line filters
for installations and systems
Rated current 6 to 125 A
Series/Type: Date: B84131 January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS' prior express consent is prohibited.
4-line filters for installations and systems
Power line filters for 3-phase systems Rated voltage 440/250 V AC, 50/60 Hz Rated current 6 to 125 A Construction
4-line filter Metal case
B84131
Features

High insertion loss Compact, cost-optimized design Easy to install ENEC10, UL and CSA approval
Applications
Power supplies for
- data systems, telecom systems - medical equipment, industrial installations - copiers Terminals
Tab connectors 6.3 x 0.8 mm Screw terminals
Marking Marking on component: Manufacturer's logo, ordering code, rated voltage, rated current, rated temperature, climatic category, date code Minimum marking on packaging: Manufacturer's logo, ordering code Circuit diagram
LINE L1 L2 L3 LOAD L1' L2' L3'
N
N
SSB0338-G
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
4-line filters for installations and systems
Technical data and measuring conditions Rated voltage VR Rated current IR Test voltage Vtest Leakage current lleak Climatic category (IEC 60068-1) Approvals 440/250 V AC, 50/60 Hz Referred to 40 C ambient temperature 1770 V DC, 2 s (line/line) 2700 V DC, 2 s (lines/case) At 400 V AC, 50 Hz 25/085/21 (-25 C/+85 C/21 days damp heat test) EN 133200, UL 1283, CSA C22.2 No.8
B84131
Characteristics and ordering codes VR AC V 440/250 IR A 6 16 25 35 35 50 63 80 125 x = approval granted Ileak mA < 3.5 < 3.5 < 3.5 < 3.5 < 3.5 < 3.5 < 3.5 < 3.5 < 3.5 Approx. weight kg 0.8 1.5 2.3 2.3 2.3 4.5 4.5 12.5 12.5 Ordering code Approvals
B84131A0006A001 B84131M0003A116 B84131M0001G125 B84131M0001G135 B84131M0001H135 B84131M0002G150 B84131M0002G163 B84131M0004G180 B84131M0004G225
x x x x - x x x x
- x x x x x x - -
- x x x x x - -
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
4-line filters for installations and systems
Dimensional drawings B84131A0006A001 (6 A)
1621
200.5
B84131
1350.8
460.5
L3' L2' N' L1'
300.2
L2 L3 L1 N
Tab connector A6.3 x 0.8 M5 (4x)
620.5
750.2
440.2
871
LINE
LOAD
SSB0958-X-E
B84131M0003A116 (16 A)
Tab connector A6.3 x 0.8 174.5 149 15.1 104 24.6 24.6 24.6
50
13.5
52.5
440.2 M5 x 6
1)
52 14.5 750.3
SSB0339-P-E
1) Also suitable for screws with 10-32 UNF thread
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
36
130.5
4-line filters for installations and systems
B84131M0001G125, B84131M0001G135/H135 (25 A, 35 A)
140.3
23 15 149
M6 and/or 10-32 UNF
B84131
15.1
104 24.6 24.6 24.6
80
52.50.8
440.2
M5 x 6
1)
52
14.5
750.3
SSB0321-L-E
1) Also suitable for screws with 10-32 UNF thread
Type B84131M0001 G125 G135 H135
IR A 25 35 35
Screw thread M6 M6 10-32 UNF
Tightening torque Nm 3 3 2
B84131M0002G150, B84131M0002G163 (50 A, 63 A) Screw thread M6
Tightening torque 3 Nm
M6
23
141
131 28.6 24.6 24.6 24.6
48.5
440.2 M5 x 6 1) 13
65.5 1050.3
SSB0322-U-E
1) Also suitable for screws with 10-32 UNF thread
Please read Cautions and warnings and
Important notes at the end of this document.
5
01/06
21.8
122
47
33.5
4-line filters for installations and systems
B84131M0004G180, B84131M0004G225 (80 A, 125 A) Screw thread M10
Tightening torque 10 Nm
350.8
2201.2
B84131
1501.2 350.8 350.8 350.8
M10
1501.2
1600.3
1) Also suitable for screws with 10-32 UNF thread
M5 x 6 1)
1200.3
SSB0544-3-E
Please read Cautions and warnings and
Important notes at the end of this document.
6
01/06
300.5
250.5
4-line filters for installations and systems
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 6 A
100 dB B84131A0006A001 80
SSB1063-I
B84131
Filters for 16 A
100 dB B84131M0003A116 80
SSB0342-9
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
0 10 4
10 5
10 6
10 7
Hz 10 8 f
Filters for 25 A
100 dB B84131M0001G125 80
SSB1676-H
Filters for 35 A
100 dB B84131M0001G135 B84131M0001H135 80
SSB0343-H
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
0 10 4
10 5
10 6
10 7
Hz 10 8 f
Please read Cautions and warnings and
Important notes at the end of this document.
7
01/06
4-line filters for installations and systems
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical)
Filters for 50 A
100 dB B84131M0002G150 80
SSB0541-D
B84131
Filters for 63 A
100 dB B84131M0002G163 80
SSB0345-Y
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
0 10 4
10 5
10 6
10 7
Hz 10 8 f
Filters for 80 A
100 dB B84131M0004G180 80
SSB0545-B
Filters for 125 A
100 dB B84131M0004G225 80
SSB0546-J
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
0 10 4
10 5
10 6
10 7
Hz 10 8 f
Please read Cautions and warnings and
Important notes at the end of this document.
8
01/06
EMC filters Cautions and warnings
Important information Please read all safety and warning notes carefully before installing the EMC filter and putting it into operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs are not removed nor their legibility impaired by external influences. Death, serious bodily injury and substantial material damage to equipment may occur if the appro priate safety measures are not carried out or the warnings in the text are not observed. Using according to the terms The EMC filters may be used only for their intended application within the specified values in low voltage networks in compliance with the instructions given in the data sheets and the data book. The conditions at the place of application must comply with all specifications for the filter used. Warnings
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such

as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation. Danger of electric shock. EMC filters contain components that store an electric charge. Danger ous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off. The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed. Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen cies that may cause resonances etc. can lead to destruction of the filter housing. EMC filters must be protected in the application against impermissible exceeding of the rated currents by suitable overcurrent protective.
9
01/06
EMC filters Important notes
The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of passive electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of a passive electronic component could endanger human life or health (e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of a passive electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as "hazardous"). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the "General Terms of Delivery for Products and Services in the Electrical Industry" published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap, PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks.
10
01/06


▲Up To Search▲   

 
Price & Availability of B84131A0006A001

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X